DSE4220

Auto Mains (Utility) Failure Control Modules

The DSE4220 is an Auto Mains (Utility) Failure Control Module that has been developed to provide an outstanding range of features within a compact module size.

OVERALL SIZE
140 mm x 113 mm x 43 mm (5.5” x 4.4” x 1.7”)

PANEL CUTOUT SIZE
118 mm x 92 mm (4.6″ x 3.6″)

MAXIMUM PANEL THICKNESS
8.0 mm (0.3”)

WEIGHT
0.24kg

Description

Product Highlights

Clear fault indication notification via front LEDs.
Ensures all fault conditions are clearly highlighted to operators.

Front panel/PC software configuration.
Provides flexibility throughout installation and operation.

Power save mode.
Ensures the battery maintains enough power at all times.

3-phase generator sensing.
Provides true generator sensing.

3-phase generator and mains (utility) sensing.
Provides true generator and mains (utility) sensing.

600 V ph-ph nominal system compatibility.
Provides global flexibility.

Configurable DC outputs (2).
Provides multiple installation options.

Configurable digital inputs (7).
Provides multiple installation options.

Configurable staged loading outputs.
Provides full generator load control.

Fuel and start outputs.
Provides multiple installation options.

Configurable event log (15).
Provides access to historical alarms and operational status.

DSE Configuration Suite PC Software.
Provides complete user-friendly configuration and easy-to-use high-level system control & monitoring.


Specification

DC SUPPLY

CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous

CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. LEDs and backlight will not be maintained during cranking.

MAXIMUM OPERATING CURRENT
85 mA at 12 V, 80 mA at 24 V

MAXIMUM STANDBY CURRENT
40 mA at 12 V, 45 mA at 24 V

MAXIMUM SLEEP CURRENT
35 mA at 12 V, 32 mA at 24 V

MAXIMUM DEEP SLEEP CURRENT
<10 uA at 12 V, <10 uA at 24 V

MAINS (UTILITY)

VOLTAGE RANGE
15 V to 415 V AC (Ph to N)
26 V to 719 V AC (Ph to Ph)

FREQUENCY RANGE
3.5 Hz to 75 Hz

OUTPUTS

OUTPUT A (FUEL)
10 A short term, 5 A continuous,
at DC supply voltage

OUTPUT B (START)
10 A short term, 5 A continuous,
at DC supply voltage

AUXILIARY OUTPUTs C & D
2 A DC at supply voltage ­­

AUXILIARY OUTPUTS E & F
2 A DC at supply voltage ­­

GENERATOR

VOLTAGE RANGE
15 V to 415 V AC (Ph to N)
26 V to 719 V AC (Ph to Ph)

FREQUENCY RANGE
3.5 Hz to 75 Hz