DSE8710 (obsoleted)

Rear Mounted Synchronising & Load Sharing Control Module

The DSE8710 is an intelligent rear mounted auto start load share control module packed with industry leading features to enhance multi-set control. The module can be synchronised with up to 32 generators within the same system.

The control module is designed for rear panel mounting to reduce the amount of wiring on the panel door. The control module must be connected to a DSE871x mono display or a DSE8721 graphical colour display.

OVERALL SIZE
240 mm x 172 mm x 57 mm (9.4” x 6.8” x 2.2”)

WEIGHT
0.74kg

Description

Product Highlights

Independent display screen options.
Removes all connection cabling from the panel front doors.

32-set synchronisation.
Offers optimum flexibility for system expansion.

Configurable inputs/outputs (11/8).
Provides multiple installation options.

Dead bus sensing.
Provides rapid power delivery on multi-set systems.

Direct governor control.
Eliminates the requirement for external control equipment.

kW & kV Ar load sharing.
Provides controlled power delivery.

Remote communications (RS232, RS485 x2, Ethernet).
Provides secure and simple off site monitoring. All ports are continuously active.

Configurable event log (250).
Provides access to historical alarms and operational status.

Integral PLC editor.
Ensures additional applications are easily integrated into the system.

Load switching, load shedding & dummy load outputs.
Allows load options and dummy load requirements to be independently controlled.

Power monitoring (kW h, kVAr, kv Ah, kV Ar h), reverse power protection, kW overload protection.
Provides clear accurate power measurement information.

Data logging (USB Memory Stick).
Provides current and historical status information.

DSE Configuration Suite PC Software.
Provides complete user-friendly configuration and easy-to-use high-level system control & monitoring.


Specification

DC SUPPLY

CONTINUOUS VOLTAGE RATING
8 V to 35 V continuous

CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries

MAXIMUM OPERATING CURRENT
460 mA at 12 V, 245 mA at 24 V

MAXIMUM STANDBY CURRENT
375 mA at 12 V, 200 mA at 24 V

CHARGE FAIL/EXCITATION RANGE
0 V to 35 V

OUTPUTS

OUTPUT A (FUEL)
15 A DC at supply voltage

OUTPUT B (START)
15 A DC at supply voltage

OUTPUTS C & D
8 A AC at 250 V AC (Volt free)

AUXILIARY OUTPUTS E,F,G,H,I & J
2 A DC at supply voltage

GENERATOR & BUS

VOLTAGE RANGE
15 V to 333 V AC (L-N)

FREQUENCY RANGE
3.5 Hz to 75 Hz

MAGNETIC PICK-UP

VOLTAGE RANGE
+/- 0.5 V to 70 V

FREQUENCY RANGE
10,000 Hz (max)

BUILT-IN GOVERNOR CONTROL

MINIMUM LOAD IMPEDANCE
1000Ω
Fully isolated

GAIN VOLTAGE
0 V to 10 V DC
Fully isolated

OFFSET VOLTAGE
+/- 10 V DC
Fully isolated

BUILT-IN AVR CONTROL

MINIMUM LOAD IMPEDANCE
1000Ω
Fully isolated

GAIN VOLTAGE
0 V to 10 V DC
Fully isolated

OFFSET VOLTAGE
+/- 10 V DC
Fully isolated